Birmingham Heartlands Hospital

Controls Integration

Client:
NHS
Location:
Birmingham
Date:
May 7, 2025
Tags:
Niagara 4 software development
Jace 8000 controller specification and bench testing

The Challenge

Heartlands Hospital required a complete controls software development and commissioning solution for their new energy centre. The project demanded specification and programming of a Jace 8000 controller with associated Niagara N4 control software, developed to match the designer's control philosophy and aligned with electrical and mechanical drawings for a water source heat pump (WSHP) and combined air-handling unit system. The control strategy needed to be thoroughly tested before on-site deployment, and the entire system commissioned with full integration and handover.

What We Delivered

Link Energy developed a complete Niagara 4 controls solution covering software design, Description of Operation, bench testing and full system commissioning across both off-site and on-site phases.

Software Development & Des-Ops:

  • Full Tridium Niagara N4 control strategy software developed from design documentation and control philosophy
  • Comprehensive I/O points list and communications network register generated to match electrical schematics
  • Description of Operation prepared in line with the designer's requirements and refined following design team review
  • Control strategy logic meetings held to validate approach and incorporate design feedback
  • Control strategy and Des-Ops updated and finalised following technical review

Bench Testing & Configuration:

  • Jace 8000 controller sized and specified for the application
  • COM port configuration completed and verified
  • I/O point and network configuration tested to electrical schematics
  • Equipment points, circulation pump, heat meter and electricity meter networks configured and tested
  • Control strategy functional testing completed by section to verify logic operation
  • Graphical HMI/PX display produced as a visual representation of the system
  • History and alarm extensions configured (with notes on remote connection requirements for data storage and monitoring)
  • Pre-commissioning documentation prepared

Off-Site Commissioning:

  • Control wiring installation reviews to verify terminations and network topology good practice
  • Main Jace 8000 controller commissioning and integration
  • I/O commissioning and verification
  • Network commissioning (where temporary power supply available)
  • Point-to-point termination checks completed
  • Temperature sensor initialisation and verification

On-Site Commissioning:

  • System flow rate verification to design parameters
  • Control functionality verification against Description of Operation
  • BMS integration and interface testing
  • Final temperature sensor calibration and accuracy verification
  • Final equipment commissioning and operational checks
  • Completion of all commissioning paperwork and compliance documentation
  • Formal system demonstration and handover to Heartlands Hospital representatives

Results

Complete Software Solution: Fully developed Niagara N4 control strategy with comprehensive Des-Ops aligned with design philosophy and electrical specifications

Thoroughly Tested: Bench testing completed prior to site deployment, ensuring COM, I/O, network and logic functionality verified

System Integration: Jace 8000 fully commissioned with BMS integration, sensor calibration and equipment verification on site

Client Handover: Formal handover with graphical HMI, commissioning documentation and operational training completed

Ready for Operation: System operational and aligned with design performance targets